3C, 3C+3C Shield XLPE/XLPO VFD Cable
Used in frequency converter-controlled motors for control and power purposes
VFD cable organizes and protects variable frequency drive input and motor power wiring, and is designed to reduce VFD-related interference (EMI) on nearby equipment.
These shielded multi-conductor cables have a black thermoplastic elastomer (TPE) outer jacket, and are available with 4 conductors in up to 2 AWG wire size.
A variety of constructions and voltages are available including 600V, 2KV, 2KV armored & sheathed, and 8KV and 15KV medium voltage armored & sheathed. Grounding systems are offered in full conductor size, 3 symmetrical bare, and 3 symmetrical insulated. Shielding options include copper tape shield, tinned copper braid + poly aluminum tape, and tinned copper armor + aluminum poly tape. Whether onshore or offshore, in a refinery or on a platform, HWC has the right VFD power cable for your application.
0.6/1kv 4 core EMC VFD Cable
Voltage: 2kV, 5kV, 8kV, 15kV, 25kV
Type: Flat or Round
Conductor: Flexible tinned copper
Insulation: EPR (90°C)
Insulation Shielding: Tinned copper and color-coded nylon braid
Ground Check Conductor: Flexible tinned copper with yellow XLPE insulation
Ground Wires: Flexible tinned copper
Jacket: CPE or TPU
Standard: IEC, BS, DIN, VDE, ASTM, CSA or Customized
3+3Core EMC Type P Marine VFD Cable
Voltage: 2kV, 5kV
Core: 3 Core
Conductor: Flexible tinned copper
Insulation: EPR (90°C)
Insulation Shielding: Tinned copper and color coded nylon braid
Ground Conductor: Flexible tinned copper located in the center of the cable
Control Ground Conductor: Tinned Copper Conductor/EPR Insulation
Jacket: CPE (Blue, Green, Yellow, Orange, Red, Black)
0.6/1KV 3+3 Core XLPO VFD Power Cable
Voltage: 2kV, 5kV
Core: 3 Core
Conductor: Flexible tinned copper
Insulation: EPR (90°C)
Insulation Shielding: Tinned copper and color coded nylon braid
Ground Wires: Flexible tinned copper
Control Check Conductor: Tinned copper with yellow insulation located in the central of the cable
Separator Tape: Non-conducting
Jacket: CPE (Blue, Green, Yellow, Orange, Red, Black)
0.6/1kV Foil&Braid Shielded VFD Cable
Voltage: 600/1000V Type TC-ER, 90°C
Core: 3+3 Core
Conductor: Flexible tinned copper
Insulation: XLPO/XLPE
Insulation Shielding: Braid/Foil Shield with Full Size Drain Wire
Ground Conductor: One full-size tinned copper conductor with green/yellow polyvinyl chloride (PVC) insulation
Jacket: PVC
Color code: Black with number surface printed in contrasting ink
0.6/1kV Copper Tape Shielded VFD Cable
Voltage: 600/1000V Type TC-ER, 90°C
Core: 3+3 Core
Conductor: Flexible tinned copper
Insulation: XLPO
Insulation Shielding: Copper Tape Shielded
Ground Conductor:Three symmetrically placed flexible stranded tinned copper conductors in direct contact with the shield
Jacket: PVC
Color code: 262MCM and larger: black and numbered
4/0AWG and smaller: red, white, black
0.6/1kV Foil & Braid w/ Signal Pair
Voltage: 600/1000V Type TC-ER, -40C°C to 90C°
Core: Signal Pair
Conductor: Tinned Copper Conductors + Signal Pair
Insulation: XLPE
Insulation Shielding: Overall +85% TC Braid Shield
Ground Conductor: Full-sized Insulated Grounds
Jacket: PVC
Color code: Black with number surface printed in contrasting ink
| n˚ x Section (mm2) | Diameter under the braid (mm) | Overall Diameter (mm) | Weight (kg/km) |
| 4 G 1,5 | 7,0 | 10,4 | 155 |
| 4 G 2,5 | 7,9 | 11,3 | 195 |
| 4 G 4 | 9,2 | 12,4 | 260 |
| 4 G 6 | 10,6 | 14,0 | 345 |
| 4 G 10 | 12,9 | 17,2 | 595 |
| 3 x 16 + 3 G 2,5 | 13,5 | 17,2 | 670 |
| 3 x 25 + 3 G 4 | 16,8 | 21,4 | 1085 |
| 3 x 35 + 3 G 6 | 19,4 | 24,1 | 1455 |
| 3 x 50 + 3 G 10 | 22,8 | 28,0 | 2025 |
| 3 x 70 + 3 G 10 | 27,1 | 32,5 | 2650 |
| 3 x 95 + 3 G 16 | 30,5 | 36,1 | 3455 |
| 3 x 120 + 3 G 16 | 34,6 | 41,0 | 4345 |
| 3 x 150 + 3 G 25 | 38,9 | 45,5 | 5450 |
| 3 x 185 + 3 G 35 | 43,4 | 50,4 | 6755 |
| 3 x 240 + 3 G 50 | 49,2 | 56,6 | 8680 |
| 3 x 300 + 3 G 50 | 55,3 | 63,0 | 10695 |
| Size (AWG/ kcmil) |
Number of Conductor | Conductor Stranding | Insulation Thickness (inches) | Ground Wire Size (AWG) | Ground Wire Stranding | Jacket Thickness (inches) | Overall Dia. (inches) | Weight (lbs/Mft.) |
| 14 | 3 | 19 | 0.030 | 18 x 3 | 19 | 0.06 | 0.466 | 158 |
| 12 | 3 | 19 | 0.030 | 16 x 3 | 19 | 0.06 | 0.509 | 199 |
| 10 | 3 | 37 | 0.030 | 14 x 3 | 19 | 0.06 | 0.552 | 258 |
| 8 | 3 | 37 | 0.045 | 14 x 3 | 19 | 0.06 | 0.653 | 368 |
| 6 | 3 | 61 | 0.045 | 12 x 3 | 19 | 0.06 | 0.737 | 517 |
| 4 | 3 | 133 | 0.045 | 12 x 3 | 19 | 0.08 | 0.956 | 814 |
| 2 | 3 | 133 | 0.045 | 10 x 3 | 37 | 0.08 | 1.103 | 1,178 |
| 1 | 3 | 209 | 0.055 | 10 x 3 | 37 | 0.08 | 1.221 | 1,462 |
| 1/0 | 3 | 266 | 0.080 | 10 x 3 | 37 | 0.08 | 1.447 | 1,886 |
| 2/0 | 3 | 323 | 0.080 | 10 x 3 | 37 | 0.08 | 1.538 | 1,951 |
| 4/0 | 3 | 532 | 0.080 | 8 x 3 | 37 | 0.11 | 1.883 | 3,102 |
| 262 | 3 | 646 | 0.065 | 6 x 3 | 61 | 0.11 | 1.981 | 3,642 |
| 313 | 3 | 777 | 0.065 | 6 x 3 | 61 | 0.11 | 2.08 | 4,658 |
| 373 | 3 | 925 | 0.065 | 6 x 3 | 61 | 0.11 | 2.215 | 5,318 |
| 444 | 3 | 1110 | 0.065 | 6 x 3 | 61 | 0.11 | 2.367 | 6,177 |
| 535 | 3 | 1332 | 0.080 | 6 x 3 | 61 | 0.11 | 2.676 | 7,787 |
| 646 | 3 | 1591 | 0.080 | 4 x 3 | 133 | 0.14 | 2.893 | 9,155 |
| 777 | 3 | 1924 | 0.080 | 4 x 3 | 133 | 0.14 | 3.164 | 10,914 |
| n˚ x Section (mm2) | Diameter under the braid (mm) | Overall Diameter (mm) | Weight (kg/km) |
| 4 G 1,5 | 7,0 | 10,4 | 155 |
| 4 G 2,5 | 7,9 | 11,3 | 195 |
| 4 G 4 | 9,2 | 12,4 | 260 |
| 4 G 6 | 10,6 | 14,0 | 345 |
| 4 G 10 | 12,9 | 17,2 | 595 |
| 3 x 16 + 3 G 2,5 | 13,5 | 17,2 | 670 |
| 3 x 25 + 3 G 4 | 16,8 | 21,4 | 1085 |
| 3 x 35 + 3 G 6 | 19,4 | 24,1 | 1455 |
| 3 x 50 + 3 G 10 | 22,8 | 28,0 | 2025 |
| 3 x 70 + 3 G 10 | 27,1 | 32,5 | 2650 |
| 3 x 95 + 3 G 16 | 30,5 | 36,1 | 3455 |
| 3 x 120 + 3 G 16 | 34,6 | 41,0 | 4345 |
| 3 x 150 + 3 G 25 | 38,9 | 45,5 | 5450 |
| 3 x 185 + 3 G 35 | 43,4 | 50,4 | 6755 |
| 3 x 240 + 3 G 50 | 49,2 | 56,6 | 8680 |
| 3 x 300 + 3 G 50 | 55,3 | 63,0 | 10695 |
VFD Cable Application Cables
Industry VFD System
Metallurgical industry
Automated Manufacturing
Food Processing Industry